Mitsubishi Electric LGH-50RVS-E Installation Instructions Manual page 28

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-50RVS-E:
Table of Contents

Advertisement

No.83, 84
Filter maintenance interval setting
Filter cleaning sign is displayed on the remote controller according to
the set interval in this function.
The interval can be set from 100 hrs to 9900 hrs depending on the
site situation.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
83
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
84
-
-
-
-
-
-
-
-
-
-
No.89, 90
CO
sensor setting - maximum side
2
It is possible to set the CO
concentration which fan speed turn into
2
4.
When it is necessary to set 50 ppm, set Function No. 90 as 1.
(For example, the target is 950 ppm, Function No. 89 is 3 and No. 90
is 1.)
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
89
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
90
-
-
Setting
Filter maintenance interval
check
setting - Thousands digit
0
0
1
1
2
2
3
3
(Factory setting)
4
4
5
5
6
6
7
7
8
8
9
9
Setting
Filter maintenance interval
check
setting - Hundreds digit
0
0
(Factory setting)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
CO
sensor setting
2
Setting
- maximum side -
check
Hundreds digit
0
600 ppm
1
700 ppm
2
800 ppm
3
900 ppm
4
1000 ppm
(Factory setting)
5
1100 ppm
6
1200 ppm
7
1300 ppm
8
1400 ppm
9
1500 ppm
10
1600 ppm
11
1700 ppm
12
1800 ppm
13
1900 ppm
14
2000 ppm
CO
sensor setting -
2
Setting
maximum side - Tens
check
digits
0
0 ppm
(Factory setting)
1
50 ppm
No.91, 92
CO
2
It is possible to set the CO
1.
When it is necessary to set 50 ppm, set Function No. 92 as 1.
(For example, the target is 950 ppm, Function No. 91 is 6 and No. 92
is 1.)
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
No.93
CO
sensor correction
2
CO
concentration can be corrected when PZ-70CSW-E or PZ-
2
70CSB-E is connected.
In this function, the control value of CO
On the other hand, No.44 is change the displayed CO
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
No.100
Initialization (No.1~99)
Set to initialize the remote PZ-62DR-E setting.
All settings which are changed by users are cancelled.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
Eng-28
sensor setting - minimum side
concentration which fan speed turn into
2
CO
sensor setting -
PZ-62DR-E
2
Setting
minimum side - Tens
check
Function No. Setting Data
digits
0
300 ppm
1
400 ppm
(Factory setting)
2
500 ppm
3
600 ppm
4
700 ppm
5
800 ppm
6
900 ppm
91
7
1000 ppm
8
1100 ppm
9
1200 ppm
10
1300 ppm
11
1400 ppm
12
1500 ppm
13
1600 ppm
14
1700 ppm
CO
sensor setting -
PZ-62DR-E
2
Setting
minimum side - Tens
check
Function No. Setting Data
digits
0
0 ppm
92
1
50 ppm
(Factory setting)
level is corrected.
2
2
PZ-62DR-E
Setting
CO
sensor analogue
2
check
correction
Function No. Setting Data
0
-250 ppm
1
-200 ppm
2
-150 ppm
3
-100 ppm
4
-50 ppm
5
93
±0 ppm
(Factory setting)
6
50 ppm
7
100 ppm
8
150 ppm
9
200 ppm
10
250 ppm
PZ-62DR-E
Setting
Initialization
check
Function No. Setting Data
0
N/A
(Factory setting)
100
1
Available
level only.