Mitsubishi Electric LGH-50RVS-E Installation Instructions Manual page 14

Lossnay heat recovery ventilator
Hide thumbs Also See for LGH-50RVS-E:
Table of Contents

Advertisement

6
When switching By-pass externally.
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E) in the connector CN26 (White).
SW1
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
With SW1 is "ON", the ventilation mode of Lossnay is changed to the
By-pass ventilation regardless of the setting on the remote controller.
When multiple Lossnay units are controlled by one input, PZ-62DR-E is
necessary.
The signal has to be input ed into main unit referring to 3.
* When the outdoor air temperature drops lower than 8˚C, it changes
to the heat recovery ventilation. (In this case, ventilation mode icon
on the display of the remote controller does not change from the
previous mode, it might be different from the actual unit operation.)
7
To change fan speed by 0 - 10 VDC input
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E) in the connector CN26 (White).
Remote controller adapter
(Optional) PAC-SA88HA-E
Not used. Insulate
completely.
Yellow 4 (0 - 10 VDC)
External
Green 5 (COM)
device
Max wiring length 10 m
To change fan speed by 0 - 10 VDC input, the wiring should be as
shown by the above picture. Refer to function settings
more details.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputed into main unit referring to 3.
CAUTION
• Make sure of correct polarity.
8
When using the remote/local switching and the ON/OFF
input (level signal)
Insert the optional remote ON/OFF adapter (PAC-SE55RA-E) in
CN32 on the Lossnay control circuit board.
When multiple Lossnay units are controlled by one input, the signal
has to be inputed into main unit referring to 3.
Remote control
board
Relay circuit
SW2
X
X
SW1
Y
Y
SW1: When this is ON, Lossnay cannot be turned ON/OFF by the
Remote Controller (PZ-62DR-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting SW2
at ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
Remote controller adapter
Lossnay
(Optional) PAC-SA88HA-E
control board
Brown 1
Red 2
CN26
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Not used. Insulate completely.
Max wiring length 10 m
Lossnay
control board
Brown 1
CN26
Red 2
Orange 3
Fan speed/
Ventilation
mode selection
for
No. 66
Remote ON/OFF adapter
Lossnay
(Optional) PAC-SE55RA-E
control board
Orange 1
CN32
Red 2
Brown 3
Max wiring length 10 m
9
When connecting to the City Multi, Mitsubishi Electric Air-
Conditioner Network System (MELANS)
TB5
S
B
A
• Connect a shielded wire to terminal TB5 S on the circuit board.
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the City Multi
• Remote Controller
PZ-62DR-E:
Connect to TM4 1, 2 on the circuit board. (See Section 1
"When connecting with remote controller (PZ-62DR-E)".)
• Securely connect the M-NET transmission cables to TB5 AB.
(No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm
CAUTION
• Do not tighten screws on the terminal block with a torque
larger than 0.5 N ・ m. It may damage the circuit board.
• Always use shielded wires only for the M-NET transmission
cables, and finish the shield properly.
• Be sure to cut M-NET power supply during Lossnay wiring,
otherwise it causes malfunction.
When interlocking with Mitsubishi M-NET air conditioner
• Incase of PZ-62DR-E
Air
conditioner
MA remote
controller
When connecting to PZ-62DR-E and MELANS
• Connect the power feeding unit.
Power
(Optional)
supply unit
* Limit the total length of transmission cables no longer than 500 m.
Limit the wiring length between Lossnay and the power supply unit
(Optional) or the outdoor unit no longer than 200 m.
Note
• LGH-RVS-E series Lossnay can NOT be set as the same
group with other series Lossnay such as LGH-RVX-E series
or LGH-RVXT-E series.
Eng-14
Shielded wire
M-NET transmission cable
indoor unit, or Mitsubishi Electric
Air-Conditioner Network System
(MELANS) - to the Lossnay.
2
Air
Lossnay
conditioner
M-NET transmission cable
PZ-62DR-E
MELANS
Lossnay
M-NET transmission cable
PZ-62DR-E