Download Print this page

GE DEH41552 Installation Instruction page 3

Undervoltage release device

Advertisement

3
STE P 6
INSTALLATION
Drop down the UVR in the right pole in locating holes
provided in Base as shown Figure 7.
Be absolutely sure to reinstall parts in their proper
location which are accidentally removed from the breaker.
Figure 7.
While dropping down the UVR in the right pole, make
sure that the UVR reset arm is properly relieved and made
to rest on the handle "L" bend extension provided as
shown in the figure 8.
Handle Yoke
"L" Bend
UVR Reset Arm
Figure 8.
STEP 7
Reinstalling Cover
Reinstall plastic breaker handle and shutter. Position the wires to
match the wire exiting hole in the cover as shown in Figure 9.
Make sure no wires are pinched in the routing.
Wires must pass through the cover notch as shown in Figure
10.
Make sure the cover
is
four
inner cover mounting screws to torque value of 12-15
Lb-in and two outer mounting screws to 18-22 Lb-in.
Figure 10.
properly
seated
and
tighten
Figure 9.
the

Advertisement

loading