Huawei FusionPower6000 Product Description page 30

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Product Description
Item
Inverter output
short-circuit
capability
Bypass overload
capability
Table 4-13 System electrical specifications
Item
Parallel system
reliability
Issue 02 (2021-06-30)
1000 kVA/1200 kVA
● Load > 150%: transfers to
bypass mode after 200 ms
or more; withstands at
least 50 shocks
If the initial load rate is less than 40%, twice the rated
current can be tolerated for 300 ms in the case of inverter
output short-circuit.
● 30°C: runs continuously at
135% load; generates
only alarms and depends
on overtemperature
protection at 135–150%
load
● 40°C: runs continuously at
125% load; generates
only alarms and depends
on overtemperature
protection at 125–150%
load
● At 40°C, if the load of the
bypass single-phase or
three-phase is 150%–
200%, the bypass will be
shut down in 5 minutes,
and the hardware
depends on
overtemperature
protection. If the load of
the bypass single-phase
or three-phase is greater
than 200%, the bypass
will be shut down in 1
minute, and the hardware
depends on
overtemperature
protection.
● Load > 1000%: runs for
100 ms
Specifications
Redundant parallel signals
Copyright © Huawei Technologies Co., Ltd.
4 Product Overview
1600 kVA
● 30°C: runs continuously
at 110% load; runs for 10
min and then depends on
overtemperature
protection at 110%–
125% load
● 40°C: runs continuously
at 100% load; generates
only alarms and depends
on overtemperature
protection at 100–125%
load
● 40°C: generates only
alarms and depends on
overtemperature
protection at 125%–
1000% load
● Load > 1000%: runs for
100 ms
24