Huawei FusionDC1000A Quick Manual page 35

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:

Advertisement

Category
Parameter
Scheduled equalized charging interval (d)
Float volt. temp. comp.
Float volt. temp. comp. coef. (mV/°C· cell)
Max. batt. dis. time (h)
Sched. shallow dis. Test
Shallow dis. test dis. ratio (%)
Undertemp. alarm thresh. (°C)
Overtemp. alarm thresh. (°C)
Battery
Parameter
Backup time warning
Settings
Remain. cap. Warning
Dis. cur. 0.1C EOD (V/cell)
Dis. cur. 0.3C EOD (V/cell)
Dis. cur. 0.5C EOD (V/cell)
Dis. cur. 1.0C EOD (V/cell)
Intelligent hibernation
Single batt. float chg. voltage deviation alarm thres.
Single batt. dis. Voltage deviation alarm thres. (%)
MUE05A connection
Batter ground fault [BTG]
D.G. connection [GEN]
Dry Contact
Settings
PDC output breaker [OUT]
PDC maintenance breaker [MT]
BP/SYSMT Switch
Default Value
1.80V/cell
1.80V/cell
1.75V/cell
1.60V/cell
(%)
/
/
/
24
/
20%
-5℃
50℃
5
20%
/
/
/
Enable
Disable
Disable
Disable
Disable
Disable
Value Range
/
/
/
16~48
/
10%—50%
-20℃ to +5℃
35℃ to 55℃
3min—30min
5%—50%
/
/
/
/
/
/
/
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Setting
Remarks
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A
Default value
N/A