Category
Frequency Thresholds
Frequency Hysteresis
Device
Configuration
Delay Times
Language Selection
Parameter
Freq Threshold Min LN1
Freq Threshold Min LN2
Freq Threshold Max LN1
Freq Threshold Max LN2
Freq Hysteresis Min LN1
Freq Hysteresis Min LN2
Freq Hysteresis Max LN1
Freq Hysteresis Max LN2
Switching
Dead Band I to II
Back Switching
Dead Band II to I
Delay on Transfer
Generator Stop
Default Value
-1%
-1%
+1%
+1%
-3.0%
-3.0%
+3.0%
+3.0%
0s
0s
0s
0s, 1s...59s, 1 min, 2 min...90 min
0s
0s
0s, 1s...59s, 1 min, 2 min...10 min
5s
0s, 1s...59s, 1 min, 2 min...30 min
English, French, Italian, Spanish, Finnish, German, Russian and
Chinese
Value Range
-10% to -1%
-10% to -1%
+1% to +10%
+1% to +10%
-9.8% to -0.8%
-9.8% to -0.8%
+0.8% to +9.8%
+0.8% to +9.8%
0–60s
0–60s
0–60s
Chinese
Setting
Remarks
-5%
N/A
-5%
N/A
+5%
N/A
+5%
N/A
-3.0%
N/A
-3.0%
N/A
+3.0%
N/A
+3.0%
N/A
0s
N/A
5s
N/A
0s
N/A
5s
N/A
30s
N/A
10s
N/A
English
N/A