FusionModule2000 Smart Modular Data Center
Product Description
7.4.2 Operating Environment Requirements
Physical ports
Table 7-17 Physical ports
Item
Indoor unit
Outdoor unit
water cooling
module
Low-temperat
ure component
(optional
component)
Issue 06 (2020-05-21)
−
Compared with a traditional electrode humidifier, the wet film humidifier has a
longer service life and maintenance interval.
Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
Check valve
The check valve effectively prevents gas or liquid backflow.
Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers an alarm,
prompting for air filter replacement.
T/H sensor
Built-in negative temperature coefficient (NTC) temperature sensors and return air T/H
sensor are provided.
Refrigerant liquid pipe
Refrigerant gas pipe
Humidifier water inlet pipe
Drainpipe
Refrigerant liquid pipe
Refrigerant gas pipe
Refrigerant liquid pipe
Refrigerant gas pipe
Connecting to indoor unit
liquid pipe
Connecting to indoor unit
gas pipe
Copyright © Huawei Technologies Co., Ltd.
7 Temperature Control System
Specifications
Outer diameter of 5/8 inch (15.88 mm),
welding
Outer diameter of 7/8 inch (22.22 mm),
welding
G 1/2 inch inner screw thread (humidifier
hose is provided for the smart cooling
product)
G 3/4 inch outer screw thread (humidifier
hose is not provided for the smart cooling
product)
BSPP 1/2 inch inner screw thread
Outer diameter of 5/8 inch (15.88 mm),
welding
Outer diameter of 7/8 inch (22.22 mm),
welding
Outer diameter of 5/8 inch (15.88 mm),
welding
Outer diameter of 7/8 inch (22.22 mm),
welding
Outer diameter of 5/8 inch (15.88 mm),
welding
Outer diameter of 7/8 inch (22.22 mm),
welding