Hitachi RCI Service Manual page 29

Indoor units system free series & complementary systems
Table of Contents

Advertisement

2 Unit installation
Steel beams
Wooden beams
Thread on the nuts and fit the washers for all the bolts, as shown in the figure.
Fit two suspension brackets onto the nut and washer of each bolt, starting on one side.
Check that the nuts and washers are correctly secured with the suspension bracket retainers and fit the brackets onto their
nuts and washers on the other side.
Fit the washers with the insulation facing downwards, as shown in the figure. Bear in mind the position of the side for pipe
connection before lifting the indoor unit.
Where a false ceiling is already installed, install and prepare the pipes and cables on the indoor unit before lifting it.
C A U T I O N
Before lifting the unit, prepare any necessary means (ladders, scaffolding, elevator platform, etc.) and check
that the current safety regulations in the place where the installation is taking place are met.
Check that the lifting work can be carried out without the risk of injuries to you or others in the surrounding
area.
Request the assistance of another person to lift the unit.
17
SMGB0063 rev. 1 - 10/2010
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

RcimRcdRpcRpiRpimRpk ... Show all

Table of Contents