Adaptation To The Lighting Situation; General Lightning Settings; Flickering; Relay Settings - Bosch AVIOTEC IP starlight 8000 Operation And Commissioning Manual

Hide thumbs Also See for AVIOTEC IP starlight 8000:
Table of Contents

Advertisement

AVIOTEC IP starlight 8000
Delete Automasks
Notice!
Delete automasks if you changed the camera position, zoom, point of view or after a fire. Also
delete automasks if the spatial arrangement of objects in the detection area has changed
fundamentally.
To delete the automasks for Flame detection from the alarm memory:
1.
2.
3.
P
To delete the automasks for Smoke detection from the alarm memory:
1.
2.
3.
P
7.3

Adaptation to the lighting situation

The lighting can vary greatly from application to application. You can adjust the following
settings to the lighting situation.
7.3.1

General lightning settings

There are three different settings in the camera menu that are important for lighting in relation
to video-based fire detection:
Go to Camera > Installer Menu > Day/Night. You can select the following settings:
Auto - the camera switches the IR cut-off filter on and off depending on the scene illumination
level. Select this setting if you have continuous natural or artificial light in your application and
at last 2 lx are available or you have artificial light and redundant IR lightning.
Monochrome - the IR cut-off filter is removed, giving full IR sensitivity. Select this setting if you
have continuous IR lightning in your application.
Color - the camera always produces a color signal regardless of light levels. Select this setting
if you have continuous natural or artificial light in your application.
7.3.2

Flickering

Select the mode for automatic light-level control:
7.4

Relay settings

Notice!
The alarm output is only configurable for flame or smoke alarms. Forwarding alarms coming
from Intelligent Video Analytics is not possible.
Bosch Sicherheitssysteme GmbH
Navigate to Fire detection > Flames > Detection.
Select Off and press Set.
Select On and press Set.
Automasks for Flame were deleted.
Navigate to Fire detection > Smoke > Detection.
Select Off and press Set.
Select On and press Set.
Automasks for Smoke were deleted.
Fluorescent 50 Hz
Fluorescent 60 Hz
Outdoor
Operation and Commissioning Manual
Adjustment of detection settings | en
2020.08 | 01 | F.01U.391.015
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcs‑8000‑vfd‑b01u.317.536

Table of Contents