PDU8000 Modular Precision PDC V2.0
User Manual
Maintenance
Item
PDC interior
Oxidation of
metal
components
in the PDC

8.2 Alarm Reference

Alarm
Name
Abnormal
board
comm.
Configuring
board ...
Issue 04 (2021-04-13)
Mai
Operation
nten
Guide
ance
Inter
val
Yearl
Check
y
whether dust
has
accumulated
on the PDC
mounting
panels.
Yearl
Visual
y
observation
Alarm
Impact
Severity
Critical
The
communication
between the
MDU and
monitoring
board is
interrupted.
Warning
The MDU is
configuring the
monitoring
board.
Copyright © Huawei Technologies Co., Ltd.
Expected
Exception Handling
Result
The white
If the white paper
paper that
becomes dirty, clean the
you use to
PDC interior.
wipe the
mount
panel is
clean.
No metal
● If any metal
component
component suffers
rusts.
from severe oxidation,
remove the rust or
replace the
component in a timely
manner.
● If the component is
painted, repaint it
after removing the
rust.
Possible
Solutions
Cause
The
Check whether the
monitoring
CAN cable is in
board is
loose contact. If yes,
disconnecte
connect it securely.
d.
The MDU is
N/A
configuring
the
monitoring
board.