PDU8000 Modular Precision PDC V2.0
User Manual
●
Specifies the lower alarm threshold in relative to the rated voltage. The value
ranges from 75 to 95.
●
Specifies the duration for confirming an undervoltage alarm. The value ranges
from 1 to 10.
●
Specifies the overload alarm threshold in relative to the rated load. The value
ranges from 100 to 120.
●
Specifies the duration for confirming an overload alarm. The value ranges from 1
to 10.
●
Specifies the overfrequency alarm threshold in relative to the rated frequency. The
value ranges from 1 to 10.
●
Specifies the duration for confirming an overfrequency alarm. The value ranges
from 1 to 10.
●
Specifies the upper alarm threshold in relative to the rated current. The value
ranges from 80 to 100.
●
Specifies the lower alarm threshold in relative to the rated current. The value
ranges from 30 to 80.
7.4.3.6 Setting Wizard
On the Settings screen, tap Setting Wizard to access the screen.
Issue 04 (2021-04-13)
System undervoltage (%)
Undervoltage ack.time (s)
Overload (%)
Overload ack.time (s)
Overfrequency (Hz)
Overfrequency ack.time (s)
Upper load cur. thre. (%)
Lower Load cur. thre. (%)
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
94