A1 Status; Network Status; Generator Status - GE Multilin 489 Instruction Manual

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

6.2

A1 Status

6.2.1

Network Status

NETWORK STATUS
6.2.2

Generator Status

GENERATOR
6–4
Courtesy of NationalSwitchgear.com
PATH: ACTUAL VALUES
A1 STATUS
[ ]
Ethernet Lnk Con Dia
Status
This actual value appears when the relay is ordered with the Ethernet (T) option.
The
actual value message indicates the status of the Ethernet link,
ETHERNET STATUS
connection, and diagnostic via three indicators. The
symbol indicates off. There is also a blinking indication.
The box under
column indicates the Ethernet link status. If it is on, the Ethernet port is
LNK
connected to the network; if it is off, the port is disconnected. This indicator is normally on.
The box under the
column indicates the connection status. If on, the Ethernet port is
CON
configured and ready to transmit and receive data. If blinking, the Ethernet port is either
active (transmitting or receiving data) or indicating an error if the diagnostic status is also
on or blinking.
The box under the
column indicates the diagnostic status. If it is on, then either a fatal
DIA
Ethernet port error has occurred or there is a duplicate IP address on the network. If
blinking, then there is a non-fatal network error. Off indicates no errors.
PATH: ACTUAL VALUES
A1 STATUS
GENERATOR STATUS:
[ ]
Offline
GENERATOR THERMAL
MESSAGE
CAPACITY USED: 0%
ESTIMATED TRIP TIME
MESSAGE
ON OVERLOAD: Never
These messages describe the status of the generator at any given point in time. If the
generator has been tripped, is still offline, and the 489 has not yet been reset, the
will be "Tripped". The
GENERATOR STATUS
reflects an integrated value of both the stator and rotor thermal capacity used. The values
for
ESTIMATED TRIP TIME ON OVERLOAD
up on the overload curve.
CHAPTER 6: ACTUAL VALUES
NETWORK STATUS
Range: see description below
[ ] [ ] [ ]
symbol indicates on, and the
[ ]
GENERATOR STATUS
Range: Online, Offline, Tripped
Range: 0 to 100%. Seen only if the
Thermal Model is enabled
Range: 0 to 10000 sec., Never. Seen
only if the Thermal Model is
enabled
GENERATOR THERMAL CAPACITY USED
will appear whenever the 489 thermal model picks
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
[ ]
value