Parameter Descriptions
O-13 Configurable Status Word STW
Array [16]
Option:
Function:
[65] Comparator 5
See parameter group LC-1# Comparators. If
comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic Rule 0
See parameter group LC-4# Logic Rules. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71] Logic Rule 1
See parameter group LC-4# Logic Rules. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72] Logic Rule 2
See parameter group LC-4# Logic Rules. If
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73] Logic Rule 3
See parameter group LC-4# Logic Rules. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic Rule 4
See parameter group LC-4# Logic Rules. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic Rule 5
See parameter group LC-4# Logic Rules. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL digital out
See parameter LC-52 Logic Controller Action.
A
The output goes high whenever the smart
logic action [38] Set digital out A high is
executed. The output goes low whenever
the smart logic action [32] Set digital out A
low is executed.
[81] SL digital out
See parameter LC-52 Logic Controller Action.
B
The input goes high whenever the smart
logic action [39] Set digital out B high is
executed. The input goes low whenever the
smart logic action [33] Set digital out B low
is executed.
[82] SL digital out
See parameter LC-52 Logic Controller Action.
C
The input goes high whenever the smart
logic action [40] Set digital out C high is
executed. The input goes low whenever the
smart logic action [34] Set digital out C low
is executed.
[83] SL digital out
See parameter LC-52 Logic Controller Action.
D
The input goes high whenever the smart
logic action [41] Set digital out D high is
executed. The input goes low whenever the
smart logic action [35] Set digital out D low
is executed.
[84] SL digital out
See parameter LC-52 Logic Controller Action.
E
The input goes high whenever the smart
logic action [42] Set digital out E high is
executed. The input goes low whenever the
DET-618D
AF-650 GP™ Programming Guide
O-13 Configurable Status Word STW
Array [16]
Option:
[85] SL digital out
F
[86] ATEX ETR cur.
alarm
[87] ATEX ETR freq.
alarm
[88] ATEX ETR cur.
warning
[89] ATEX ETR freq.
warning
O-14 Configurable Control Word CTW
Array [15]
Option:
[0]
None
[1]
Profile
*
default
[2]
CTW
Valid,
active low
[4]
PID error
inverse
[5]
PID reset
I part
[6]
PID
enable
02/2016 All rights reserved.
Function:
smart logic action [36] Set digital out E low
is executed.
See parameter LC-52 Logic Controller Action.
The input goes high whenever the smart
logic action [43] Set digital out F high is
executed. The input goes low whenever the
smart logic action [37] Set digital out F low
is executed.
Function:
This parameter is not valid in software versions
before 4.93.
The frequency converter ignores the information
in this bit.
The functionality of the bit is depending on the
selection parameter O-10 Control Word Profile.
If set to 1, the frequency converter ignores the
remaining bits of the control word.
Inverts the resulting error from the process PID
controller. Available only if
parameter H-40 Configuration Mode is set to [6]
Surface Winder, [7] Extended PID Speed OL, or [8]
Extended PID Speed CL.
Resets the I-part of the process PID controller.
Equivalent to parameter PI-40 Process PID I-part
Reset. Available only if parameter H-40 Configu-
ration Mode is set to [6] Surface Winder, [7]
Extended PID Speed OL, or [8] Extended PID Speed
CL.
Enables the extended process PID controller.
Equivalent to parameter PI-50 Process PID
Extended PID. Available only if
parameter H-40 Configuration Mode is set to [6]
Surface Winder, [7] Extended PID Speed OL, or [8]
Extended PID Speed CL.