ABB Relion 670 Series Applications Manual page 599

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
SMAI1:37:
DFTReference = DFTRefGrp6 for SMAI1:37 to use SMAI6:42 as reference (see Figure 284)
SMAI2:38 – SMAI12:48:
24.12
Test mode functionality TESTMODE
24.12.1
Application
The protection and control IEDs may have a complex configuration with many included
functions. To make the testing procedure easier, the IEDs include the feature that allows
individual blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enables the
user to follow the operation of several related functions to check correct functionality and to
check parts of the configuration, and to check parts.
24.12.1.1
IEC 61850 protocol test mode
The function block TESTMODE has implemented the extended testing mode capabilities for
IEC 61850 Ed2 systems. Operator commands sent to the function block TESTMODE determine
the behavior of the functions. The command can be given remotely from an IEC 61850 client or
from the LHMI under the Main menu/Test/Function test modes/Communication/Station
Communication/IEC61850 LD0 LLN0/LD0LLN0:1. The possible values of the function block
TESTMODE are described in
2 .
There is no setting in PCM600 via PST for the TESTMODE function block.
The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under Main menu/Test/
Function test modes/Communication/Station communication/IEC61850 LD0 LLN0/
LD0LLN0:1 to
When the setting of the DataObject Mod is changed at this level, all Logical Nodes inside the
logical device update their own behavior according to IEC61850-7-4. The supported values of
the function block TESTMODE are described in
Edition 2 . When the function block TESTMODE is in test mode the Start LED on the LHMI is
turned on with steady light.
The parameter
Function test modes/Communication/Station Communication
The parameter Mod can be set on the LHMI to the same values as for the DataObject Mod of
the Root LD.LNN0 to
Function test modes/ Differential protection/GeneratorDiff(87G,3Id/I>)/ GENPDIF(87G,3Id/
I>):1.
It is possible that the behavior of the function block TESTMODE is also influenced by other
sources as well, independent of the mode communicated via the IEC61850-8-1 station bus. For
Bay control REC670
Application manual
DFTRefExtOut = DFTRefGrp6 to route SMAI6:42 reference to the SPFCOUT output,
DFTReference = DFTRefGrp6 to use SMAI6:42 as reference.
Communication protocol manual, IEC 61850 Edition 1 and Edition
To be able to set the function block TESTMODE remotely, the setting via path
on LHMI and in PST: Main menu/Configuration/Communication/ Station
Communication/IEC61850-8-1/IEC61850-8-1:1
Off . The possible values of the parameter RemoteModControl are Off ,
set to
Maintenance or All levels . The Off value denies all access to function block
TESTMODE from remote,
originator (orCat) is
On , Off , TestBlocked , Test or Blocked .
Mod of any specific function block can be configured under Main menu/Test/
On , Off , TestBlocked , Test or Blocked . For Example, Main menu/ Test/
© Copyright 2017 Hitachi Power Grids. All rights reserved
Maintenance requires that the category of the
Maintenance and All levels allow any orCat.
Communication protocol manual, IEC 61850
Basic IED functions
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v5
RemoteModControl may not be
Section 24
IP1647-1 v3
M11407-3 v9
593