merging unit according to IEC 61850-9-2 is used instead of the TRM, this parameter shall be
set to 5.
CompRange should be set such that the maximum through-fault current falls within this range.
Therefore,
When the
differential current during external fault.
Bay control REC670
Application manual
CompRange should be set to nearest value >/= √2* Maximum through-fault current.
CompRange is set below the maximum through-fault current, it can create false