Huawei NetCol8000-E220 User Manual page 89

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Issue 06 (2020-08-19)
Parameter
Rotation
time
Forced
rotation
Requirement
control
Cascade
function
Differential
pressure
sharing
Cold aisle
temperature
and humidity
sharing
Hot aisle
temperature
and humidity
sharing
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Setting Guide
0 by default
This item is set to No by
default. If forced rotation
is required, the function
is set to Yes.
Anti-competitive
running is recommended
for the following
scenario: In one
teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
If the heat load to the
device increases, the
cascade function is
recommended.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with differential pressure
sensors.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with cold aisle T/H
sensors.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with hot aisle T/H
sensors.
Default Value
0
No
Disable
Disable
Disable
Disable
Disable
80