7.9
STATIC TIM E-DELAY U N DERVOLTAGE
The static time-delay undervoltage system consists of a
time-delay unit which controls an instantaneous under­
voltage device. The time-delay unit is separately mounted
in the switchgear and the undervoltage device is mounted
on the breaker. Table 5 lists the catalog numbers available.
If the a-c control voltage is any voltage other than
208/240V ac, a control power transformer (also remotely
mounted with respect to the breaker) m ust be used. This
must have a minimum rating of 100 volt-amperes.
CAT. NO.
TAKYUVT- 1
TAKYUVT-2
TAKYUVT-3
INSERT W I R E
GAGE
±
005 D I A
.201
P I N
across term inals No. 1 and No. 2 of the static delay box.
The coi l of the tri ppi ng unit is connected across term inals
No. 4 and No. 5 of the static box through the secondary
disconnects of the breaker. The secondary d isconnects to
be used will be shown on the breaker wiring diagram.
be used i n conjunction with one static time-delay unit.
with a thermotector control unit. Overheating of motor win­
dings causes the thermotector, imbedded in the motor win­
dings, to open. This de-energizes the undervoltage device
on the breaker and drops the motor load.
7.9.1 ADJUSTMENTS
recommended to determine whether the undervoltage
device on the breaker of the static time delay unit is the
faulty component.
static box. See Table 5 for these values.
undervoltage device connected. See Table 5 for values.
TAB L E 5
TI M E-DELAY U N ITS
CONTROL
APPROXIMATE STEADY STATE
VOLTAGE
DC OPERATING VOLTAGE
TERMINALS
1 & 2
1 25 VDC
250VDC
208/240 VAC
FIG. 320 - POSITIVE TRIP CHECK
When i nstalled, the voltage to be monitored is connected
No more than one undervoltage tri pping device should
The static time-delay undervoltage can also be furnished
In the event the system fails, the following checks are
1. Check input voltages across term inals 1 and 2 on the
2. Check output voltages on termi nals 4 and 5 with the
TERMINALS
4 & 5
50
1 00
1 1 0/ 1 25
STOP
NOMINAL DC COIL
R ESISTANCE
(OHMS)
@ 25°C
440
1 600
1 600
25