Mount The Charger; Wall Wall Mount; Rack Rack Mount - GE Integritas 3TL125-SACY-D10Y-P000 Quick Start Manual

Wall mount 3 rectifier battery charger
Table of Contents

Advertisement

Step 2—Mount the Charger
The Charger may be mounted on a wall or in a rack, in an area free of flammable/explosive materials.
Recommended Clearance: Above and Below the charger: 2 inches (5 cm),
Hot air exits the top—do not locate temperature sensitive equipment above the charger.
CAUTION Use safe lifting practices. The charger is heavy—up to 154 lb (70 kg). Lifting devices are recommended.
Wall Mount—follow Step 1Wall.
Rack Mount—follow Step 1R.
Step 2 Wall—Mount the Charger to a Wall
CAUTION Use safe lifting practices. The charger is heavy. Lifting devices are recommended.
The wall and fasteners must safely support 470 lb (3 times the charger weight).
Mount with 8 sets of mounting hardware rated for at least 60 lb each.
1. Locate appropriate place for the charger.
2. Secure the bottom wall mount bracket to the wall.
a. Remove the bottom wall mount bracket from the charger—4 screws.
b. Drill 4 holes in the wall to mount the bottom bracket.
Use the bottom bracket as a template.
c. Secure the bottom bracket to the wall with mounting hardware.
3. Prepare to secure the top wall mount bracket to the wall.
a. Place the charger against the wall, resting on the wall mounted bottom bracket.
b. Temporarily install one screw through the bottom bracket into the charger..
c. Mark 4 holes in the wall for top bracket mounting hardware.
Use the top bracket as a template.
d. Remove the charger, first removing the screw installed in step b.
e. Drill 4 holes in the wall to mount the top bracket.
4. Secure the charger to the wall.
a. Place the charger against the wall, resting on the bottom secured bracket.
b. Secure the top bottom bracket to the wall with mounting hardware.
c. Secure the cabinet to the bottom bracket with the 4 screws removed in step a.
Go to Step 3
Step 2 Rack—Mount the Charger to a Rack
CAUTION Use safe lifting practices. The charger is heavy. Lifting devices are recommended.
1. Attach Rack Mount Brackets positioned for flush mount or mid-mount.
Secure mounting brackets—8 screws each.
Torque to 25 in-lb (2.8 Nm)
2. Attach the system to the frame using a minimum of twelve (six on each side) 12-24 screws (provided).
Torque to 35 in-lb (4.0 Nm) - 5/16" socket.
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r04 2019 May
In Front of the charger: 36" (914 mm).
5

Advertisement

Table of Contents
loading

Table of Contents