Step 6—Connect Batteries
Danger:
Energy Hazard—avoid shorting battery wires to ground or to each other.
Caution: Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and cause a short circuit.
Battery voltage is marked on the charger ratings label.
DC Output Box location:
Bottom Feed—bottom right
DC knockouts: for 2" conduit.
Wire Gauge: 6AWG to 1/0
1. Measure battery voltage and polarity with a meter.
2. Verify all DC breakers (DC1 and DC2 / BATT if present) are OFF.
3. Remove the DC Output Box cover - 4 thumbscrews.
4. Connect Battery Positive cable to the terminal block position marked BAT1
5. Connect Battery Negative cable to the terminal block position marked BAT1
battery).
6. Repeat from 1 for second battery if present.
7. Turn BATT breaker ON if present.
8. Verify the Reverse Polarity LED is not Red and the Ready LED is Green.
If the Reverse Polarity LED is RED, reverse battery cables.
If Ready LED is not Green, verify the voltage on the battery wires.
9. Turn BATT breaker OFF if present.
Screws
Output Sig-
nal Unit
Battery TB
with 2 DC Load breakers
(Shown with +/- 125VDC)
10
Top Feed—top right
Strip Length: 1" (24 mm)
Bottom Feed
Integritas Wall Mount Charger - Quick Start Guide
Document 8600092587P r03 2018 August
Torque Screw to 70 in-lb (8 Nm)
+
+
(BAT2
for second battery).
– (
BAT2
with 1 DC Load breaker
for second
Reverse
Polarity LED
Ready LED
Output Signal Unit
Top Feed
Screws
Battery TB