Connect the AGPS board as follows:
• Remove the enclosure cover by undoing the fixing screws (1).
• Ground the unit via the bottom plate of the enclosure or via terminal X1:1 of the
AGPS board.
• Connect the cable delivered with the kit between terminal X2 of the AGPS board
(2) and drive terminal X41.
WARNING! Use only the AGPS cable delivered with the kit. Using another cable or
modifying the cable may cause a malfunction of the drive.
• Connect a cable between connector X1 of the AGPS board (3) and the
115...230 V AC source.
• Fasten the enclosure cover back with screws.
115...230 V AC
3
Installation of the AGPS board (Prevention of unexpected start-up, +Q950)
1
2
X2
79