Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 101

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:

Advertisement

Monitoring
Data
Device Name
Device
Type
Collector_EC
FE
Air Conditioner-D1
C800
Collector_EC
FE
UPS-1
C800
Collector_EC
FE
UPS-2
C800
Collector_EC
RS485
AI/DI Module-1
C800
Collector_EC
Dry
Door Status
C800
contact
Sensor-1
Collector_EC
Dry
FAULT RELAY
C800
contact
Collector_EC
Dry
Door Status
C800
contact
Sensor-2
Collector_EC
Dry
LOCAL FIRE
C800
contact
Collector_EC
Dry
FIRE RELAY
C800
contact
Collector_EC
Dry
Water Sensor-1
C800
contact
Device
Device IP
Device
Model
Address
Address
NetCol5000-
A021HN12D2
N/A
N/A
E120E1
UPS5000-E-
N/A
N/A
60K-LABBS
UPS5000-E-
N/A
N/A
60K-LABBS
EN1MMEEM
N/A
1
02A
POLYMR
M520/
N/A
N/A
GREYSTON
E GS-06
SIGMA
XT/K11031M
N/A
N/A
2
POLYMR
M520/
N/A
N/A
GREYSTON
E GS-06
SIGMA
XT/K11031M
N/A
N/A
2
SIGMA
XT/K11031M
N/A
N/A
2
GREYSTON
E WD-
N/A
N/A
900D/POLYM
RY W517K
WebUI User
LCD User
Alarm
Name and
Name and
Threshold
Password
Password
User name:
Admin
N/A
N/A
Initial
password:
000001
User name:
User name:
Admin
admin
N/A
Initial
Initial password:
password:
Changeme
000001
User name:
User name:
Admin
admin
N/A
Initial
Initial password:
password:
Changeme
000001
N/A
N/A
N/A
Normal: closed
N/A
N/A
Alarm: open
Normal: open
N/A
N/A
Alarm: closed
Normal: closed
N/A
N/A
Alarm: open
Normal: open
N/A
N/A
Alarm: closed
Normal: open
N/A
N/A
Alarm: closed
Normal: closed
N/A
N/A
Alarm: open
Port to
Upper-
DDF
Upper-
Upper-
Level
Transfer
Level
Level
Device
Port
Device
Device
Port
Smart ETH
FE
N/A
POE_4
Gateway-2
Smart ETH
FE
N/A
POE_1
Gateway-3
Smart ETH
FE
N/A
POE_2
Gateway-3
Collector_E
COM3/1
COM_IN
N/A
CC800
2V
Crimped
Collector_E
COM1/A
N/A
terminal
CC800
IDI_4
Crimped
Collector_E
N/A
AIDI_1 Extinguishant Control Panel
terminal
CC800
Crimped
Collector_E
COM2/A
N/A
terminal
CC800
IDI_5
Crimped
Collector_E
N/A
AIDI_2 Extinguishant Control Panel
terminal
CC800
Crimped
Collector_E
N/A
AIDI_3 Extinguishant Control Panel
terminal
CC800
AI/DI
RJ45
N/A
AI/DI_1
Module-1
Remarks
Settings > Comm Settings >
IP Settings
Set IP assigning mode to
Automatic (DHCP).
Settings > Comm Settings >
IP Settings
Set IP assigning mode to
Automatic (DHCP).
Settings > Comm Settings >
IP Settings
Set IP assigning mode to
Automatic (DHCP).
Baud rate: 9600
Data bits: 8
Parity check bit: None
Stop bit: 1
N/A
N/A
N/A