Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Item
DO output
DI input
RS485 serial
port
expansion
Wiegand
interface
BLINK
button
Address DIP
switch
E-label
Indicators
Table 3-70 describes the access actuator indicators.
Table 3-70 Access actuator indicator description
Indicato
r
PWR
RUN
Issue 04 (2017-06-30)
Specifications
button
One 12 V DC power output that controls magnetic locks, phoenix terminal
One DI input port for connecting to the door status switch
Two RS485 ports (one route) with the default communications rate of
9600 bit/s, physical port cascading supported (reserved function)
Two Wiegand interfaces, 12 V DC card reader operating power output;
two routes of card readers can operate at the same time.
Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network and start
networking.
Hold down the button for more than 6 seconds to clear network
parameters.
4-pin address DIP switch
Supported
Color
Name
Green
Power input
status
indicator
Green
Communicati
on status
indicator
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power is abnormal or the
board program is loading.
Blinking at
The access actuator successfully
long intervals
registers with the ECC800 and
the software runs properly (the
indicator blinks at 0.5 Hz, on for
1s and then off for 1s).
Blinking at
The communication is
short intervals
disconnected or the access
actuator fails to register with the
ECC800 (the indicator blinks at
4 Hz, on for 0.125s and then off
for 0.125s).
3 System Architecture
103