User Function - Siemens Cerberus CS1140 Commissioning

Fire detection system. commissioning ’extinguishing’
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

4

User function

Table 5: Notes on parameterization 'Extinguishing' via SWE11
Function
Outline description
Valve on: confirmation:
Line 'Extinguishing activated'
'Active' status generates î
Key stop/block:
Function line 'Stop /Blocking key'
'Active' status generates î
Activation time:
Duty cycle of activating agent valve
(Activating device 2)
Flooding time:
Flooding time
(Duty cycle of activating device 1)
Evacuation time:
Evacuation time
(Delay to activating device 1)
Stop –> evacuation time:
Function 'Stop key active' generates
during 'Evacuation' î
Horn activation:
Activation and runninng mode of
alarm horn
Silence:
Function 'Switch off alarm horn'
(Blocked during 'Flooding'+ Evacuat. )
Warning panel mode:
Deactivating and running mode of
warning panel
Extinguishing agent LOSS:
Line 'Extinguishing agent loss'
Status 'Active' generates î
Stop key FAULT:
Line 'Stop-/blocking key'
Open line / short circuit generates î
LED 'Operation':
'Power on' indicator
Local extinguish. control panel (B3Q440)
key switch:
Function 'Key switch'
Local extinguish. control panel (B3Q440)
supply FAULT:
'Fault power supply' indicator
Local extinguish. control panel (B3Q440)
1)
Default values are laid down according to each country
2)
Function variant 'Blocking key' may be used only with software V4.xx
3)
Running mode 'pulsating' only with software V5.xx (EP5) onwards
Note
In order that the combined indicators for 'Extinguishing'
are displayed on the AlgoPilot, the corresponding 'panel
variant' must be selected at CT or CI level
(for details see HELP AlgoWorks).
Fire & Security Products
Siemens Building Technologies Group
Choice of variants
a) No message (Line unused / Message 'simulated')
b) Message 'Extinguishing activated' or signal contact existent
a) autom.+ man. activation of extinguishing blocked (= 'Stop key')
b) Autom. activation of extinguishing blocked (= 'Blocking key')
a) Active for 0..240sec
b) Active until reset
a) Active for 0..240sec
b) Active until reset
a) 0..240sec
a) Evacuation time is reset (New start)
b) Evacuation time is not reset
a) activated upon 'pre-alarm' and 'evacuation' and 'actuated'
b) activated upon 'evacuation' and 'actuated'
c) running mode continuous
d) running mode pulsating upon 'pre-alarm'
e) running mode pulsating upon 'evacuation' and 'actuated'
f) running mode pulsating upon 'pre-alarm' / 'evac.' / actuat.'
a) Can be carried out via CT or extinguishing control panel
b) Can only be carried out via extinguishing control panel
a) active until RESET (no switching off via B3Q440)
b) active until switched off via B3Q440
c) running mode continuous
d) running mode pulsating
b) Fault AND 'Autom. + man. activation of extinguishing blocked'
a) Fault
a) Fault
b) Fault AND 'Autom. + man. activation of extinguishing blocked'
a) Inactive upon 'Fault' / 'Extinguishing blocked' / 'Alarm'
b) always active
a) No influence on the 'Switch off sounder' key
b) Influence on 'Switch off sounder' key
a) active upon 'Power supply fault' control unit
b) Spare indicator
Combined indicators
'Extinguishing' common
(Value 0..240 permissible)
(value 255 entered)
(Value 0..240 permissible)
(Value 255 entered)
(Value 0..240 permissible)
to all extinguishing
SECTIONS
SWE11
Value Def.
0
1
1
0
0
2)
1
0..240
120
255
0..240
30
255
0..240 16
0
0
1
a + c
0
0
a + d
8
a + e
16
3)
a + f
24
3)
b + c
1
3)
b + e
17
0
2
2
a + c
1
1
a + d
9
b + c
4
3)
b + d
12
0
0
1
0
0
1
0
1
1
0
1
1
0
1
1
ALARM
Evacuation
Extinguishing
activated
blocked
blocked
e1456c
12.1997
1)
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents