Dual Class A Initiating Circuit Module
1
Notices
These instructions cover the installation of the D129 Dual Class A Initiating Circuit module as
an interface to specified combined Burglary/Fire control panels for fire alarm and waterflow
alarm applications.
Install, test and maintain the module according to these instructions, NFPA 72, local codes,
and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in
failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible
for improperly installed, tested or maintained devices.
Before installing the module, become familiar with the Installation and Operation Guide for
the control panel you are using.
Warning!
Follow these instructions to avoid personal injury and damage to equipment.
!
NFPA 72 requires that you perform a complete system wide functional test following any
modifications, repair, upgrades or adjustments made to the system's components, hardware,
wiring, programming and software/firmware.
Bosch Security Systems, Inc.
Installation instructions
Notices | en
3
2020.04 | 04 | F.01U.362.295