Download Print this page

Bosch D129 Installation Instructions Manual page 10

Dual class a initiating circuit module

Advertisement

10
en | Programming
6
Programming
On the GV4, GV3, and GV2 panels for waterflow alarm installations where the control panel
provides the only means for operating a local sprinkler warning bell, use Point Index 2 from
the default program. This point index is programmed to:
To silence the bell while there is still a waterflow condition use Point Index 2 from the default
program, except turn Ring Until Restored to NO.
2020.04 | 04 | F.01U.362.295
Ring the bell until restored,
Buzz on Fault, Fire Point,
have a trouble condition on an open, and
have an alarm on a short.
Installation instructions
Dual Class A Initiating Circuit Module
Bosch Security Systems, Inc.