2.3 External Environment Requirements
2.4 Power Distribution Requirements
Table 2-1 Power input voltage and frequency requirements
Frequency
(Hz)
50
60
2.5 Grounding Requirements
Issue 02 (2017-01-10)
Temperature: –15° C to +52° C.
Relative humidity: 5%–95% RH.
Solar radiation: ≤ 1120 W/m
Altitude: < 3000 m; derated when the altitude exceeds 1000 m.
For the derating details, contact Huawei technical support.
Huawei recommends that YJV22 (4 x 50 mm
input power cables.
Applies to two mutual-backup inputs, namely, two mains supplies, or one mains supply
and one diesel generator (DG) supply.
A class B surge protective device (SPD) with a maximum discharge current (I
kA (8/20 µs) is required for the upstream input PDC for the FusionModule1000.
The main input power cables can be buried underground or routed on an external cable
tray.
The power input current must be 160 A.
requirements. Huawei provides products based on the voltage system and frequency
required by customers.
Input Voltage (V)
380
Compliant
Compliant
For the detailed power distribution requirements, refer to the solution in use.
The external ground resistance of the container must not exceed 10 ohms, or the
equivalent radius of the ground grid is no less than 5 m.
The upper end of the pre-installed ground grid must be at least 0.7 m underground. In
cold areas, the ground electrodes must be buried under the frozen layer.
At least two ground points on each container must be properly grounded.
Do not connect devices such as fuses and switches to ground cables.
Ground cables should be short, straight, and not coiled.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
.
2
+ 1 x 25 mm
Table 2-1
describes the voltage and frequency
400
Compliant
Incompliant
2 Site Requirements
2
) armored cables are used as
415
480
Compliant
Incompliant
Incompliant
Compliant
) of 60
max
3