Encoder Type
• In our example: encoder type is not applicable
• Press OK
OK
Encoder parameters
• In our example: all parameters will be set to default
• Press OK to continue
OK
Command and setpoint sources
• Command and setpoint sources are automatically determined using preset macros
• Macro parameters are stored in P015
• Select the appropriate macro according to your wiring
• In our example: "standard macro with analog setpoint and the ON command on the digital input 0"
• Press OK to continue
Standard IO with analog setpoint
OK
Minimum speed
• Enter the appropriate minimum speed
• We recommend that 20 % of the synchronous speed is selected
• In our example: "300 rpm" (rated speed is 1350 rpm, and synchronous speed is 1500 rpm)
• Turn the wheel to select the appropriate the numbers
• Press OK to confirm the number
300 rpm
OK
OK
OK
47