Mitsubishi Electric AE-200A Instruction Book page 26

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Item
Fan speed of interlocked
LOSSNAY
Prohibit Remote Controller
Operation
Schedule
Hold
Filter Sign
WT07190X01
Touch
or
to adjust the fan speed of the interlocked LOSSNAY unit (ventilator).
Note: For a group that is not connected to an interlocked LOSSNAY unit (ventilator), this
item will not appear.
Note: It takes a while for the status of the LOSSNAY unit group icons on the [Floor] or [Block]
display to be updated.
The following operations or setting change from the local remote controllers can be
prohibited.
ON/OFF
Operation mode
Set temperature
Filter Sign
Air Direction
Fan Speed
Timer
Note: The settable items depend on the unit model.
Note: When the [ON/OFF] operation is prohibited and the "Automatic recovery after power
failure" switch on the indoor unit is set to "Turn off the power, or restore operation
regardless of the operation status immediately before power failure," the operation of
the indoor unit will not be restored, even when turned on after power restoration.
When the switch is set to "Turn off the power, or restore operation if the unit was in
operation immediately before power failure," the operation of the indoor unit will be
restored regardless of whether the [ON/OFF] operation is prohibited or not.
Refer to the indoor unit Installation Manual for details about switch settings.
Touch [Available] or [Not Avail.] to enable/disable the scheduled operations. When the
Schedule is enabled, the scheduled operations are disabled.
Note: The operations that have been scheduled on the remote controller will not be
disabled.
Touch [ON] or [OFF] to enable/disable the Hold function. When the Hold function is
enabled, the scheduled operations are disabled.
Note: The operations that have been scheduled on the remote controller will also be
disabled.
Note: [Hold type] can be specified on the [Advanced] screen.
Note: The Hold function can be used on the AE-200A/AE-50A, but not on the
AE-200E/AE-50E.
Touch [Reset] to switch between resetting and not resetting the filter sign after cleaning
the filter.
Note: If a filter sign in the group has not been triggered, then this item will not appear.
Note: Filter sign of LOSSNAY units will not be reset.
26
Description
(Permit)
(Prohibit)