Siemens SIMATIC ET 200MP Manual page 42

Analog input module ai 8xu/i/r/rtd ba
Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

Article number
Errors/accuracies
Linearity error (relative to input range), (+/-)
Temperature error (relative to input range), (+/-
)
Crosstalk between the inputs, max.
Repeat accuracy in steady state at 25 °C (rela-
tive to input range), (+/-)
Operational error limit in overall temperature
range
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Resistance, relative to input range, (+/-)
Resistance thermometer, relative to input
range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
Current, relative to input range, (+/-)
Resistance, relative to input range, (+/-)
Resistance thermometer, relative to input
range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series mode interference (peak value of
interference < rated value of input range),
min.
Common mode voltage, max.
Common mode interference, min.
Interrupts/diagnostics/status information
Diagnostics function
Alarms
Diagnostic alarm
Limit value alarm
Diagnostic messages
Monitoring the supply voltage
Wire-break
Short-circuit
Group error
Overflow/underflow
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
6ES7531-7QF00-0AB0
0.1 %
0.006 %/K
-50 dB
0.1 %
0.5 %
0.5 %
0.5 %
Ptxxx Standard: ±1.2 K, Ptxxx Climate: ±0.8 K,
Nixxx Standard: ±0.8 K, Nixxx Climate: ±0.8 K
0.3 %
0.3 %
0.3 %
Ptxxx Standard: ±1.0 K, Ptxxx Climate: ±0.5 K,
Nixxx Standard: ±0.5 K, Nixxx Climate: ±0.5 K
40 dB
4 V
60 dB
Yes
Yes
Yes; two upper and two lower limit values in each
case
No
Yes; Only for 1 ... 5 V, 4 ... 20 mA, R, and RTD
No
No
Yes
Technical specifications