Huawei SUN2000 Series Quick Manual page 6

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

4-pin Model (100KTL/110KTL) Cable Description
No. Cable
1
PE cable
Tracking
2
system power
cable
AC output
power cable
(multi-core)
3
AC output
power cable
(single-core)
DC input power
4
cable
RS485
5
communications
cable
The value of S
is valid only if the conductors of the PE cable and AC power cable use the same
p
material. If the materials are different, ensure that the conductor of the PE cable with a proper cross-
sectional area produces a conductance equivalent to that of the cable specified in the table.
Type
Outdoor cable and M10 OT/DT
terminal
Three-core outdoor copper cable
with dual-layer protection
• If you connect a ground cable to
the ground point on the chassis
shell and the neutral wire is not
used, you are advised to use a
three-core (L1, L2, and L3)
outdoor cable and M12 OT/DT
terminals (L1, L2, and L3).
• If you connect a ground cable to
the ground point in the
maintenance compartment and
the neutral wire is not used, you
are advised to use a four-core
(L1, L2, L3, and PE) outdoor
cable, M12 OT/DT terminals
(L1, L2, and L3), and M10
OT/DT terminals (PE).
• If you connect a ground cable to
the ground point on the chassis
shell and the neutral wire is
used, you are advised to use a
four-core (L1, L2, L3, and N)
outdoor cable and M12 OT/DT
terminals (L1, L2, L3, and N).
• If you connect a ground cable to
the ground point in the
maintenance compartment and
the neutral wire is used, you are
advised to use a five-core (L1,
L2, L3, N, and PE) outdoor
cable, M12 OT/DT terminals
(L1, L2, L3, and N), and M10
OT/DT terminals (PE).
You are advised to use a single-
core outdoor cable and M12
OT/DT terminals.
PV cable that meets the 1100 V
standard
Outdoor shielded twisted pair that
meets the local standard
Recommended
Conductor Cross-
Sectional Area
≥ S/2
S
p
2
10 mm
• Copper cable
− S: 95–185 mm
− S
≥ S/2
p
• Aluminum alloy
cable or copper-clad
aluminum cable:
− S: 120–240 mm
− S
≥ S/2
p
• Copper cable
− S: 95–185 mm
• Aluminum alloy
cable or copper-clad
aluminum cable:
− S: 120–240 mm
2
4–6 mm
2
0.25–1 mm
5
Outer Diameter
N/A
15–18 mm
2
24–66 mm
2
2
14–32 mm
2
5.5–9 mm
• One or two
communications
cables: 4–11 mm
• Three
communications
cables: 4–8 mm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-110ktlSun2000-100ktlSun2000-125ktl