Reference Information; Permitted Commands / Parameters - Siemens SIMATIC S7-1500 Operating Instructions Manual

Software controller cpu 1505sp (f) ready4linux version 2.7
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Reference information

A.1

Permitted commands / parameters

To configure and operate the CPU, various commands and parameters are available for the
respective tools. This section lists the commands and parameters of the individual tools.
Commands / parameters in the CPU Control tool
To be able to use the commands, start the CPU Control tool with "./s7_cpu_control".
Command
--PowerOnCPU
--PowerOffCPU
--Run
--Stop
--GetStatus
--MemoryReset
--FactoryReset
--IP:
To be able to use the parameters, start the CPU Control tool with "./s7_cpu_control".
Parameter
--Force
--Help
Parameters in the Management tool for MAC addresses
To be able to use the parameters, start the Management tool with "./s7_vnic_macconfig".
Parameter
-m
-t
-a
-d
-h
96
Explanation
Starts the CPU in "STOP" mode.
Shut down the CPU.
Run this command before shutting down Linux. Refer to the section "CPU
behavior when shutting down the operating system (Page 75)".
Sets the CPU to "RUN" operating mode.
Sets the CPU to "STOP" operating mode.
Shows the operating state of the CPU.
Resets the CPU memory.
Resets the CPU to the factory setting.
Identifies and stores the IP address of the runtime communication interface.
Execute this command if the IP address already assigned has changed due
to a download via STEP 7.
Explanation
Skips the warning and sets the CPU to the "STOP" operating mode.
Displays the infotext in the command line editor.
Explanation
--mount-path
Parent directory of "SWCPU".
--target
Specifies the interface whose MAC address is changed.
LINUX: Siemens RT-VMM network adapter
SWCPU: Runtime communication interface
--mac-addr
Assigns a new MAC address.
--default-mac
Assigns default value for MAC address.
--help
The help and an example of how to use the tool are displayed.