Siemens RWD62 Manual

Siemens RWD62 Manual

Universal controller

Advertisement

Use
CE2N3342en
2017-12-05
RWD62
Universal Controller
For comfort control in HVAC&R-Systems
· Standalone electronic universal controller with P or PI response
· Operating voltage in accordance to type AC 24 V
· Control application selectable via Application Number
· Active input scale can be selectable
· Limit and direction of the output scale is able to be freely assigned
· Two universal inputs for Ni 1000, Pt 1000 temperature sensors and
DC 0...10 V signals
· Unit can be set as °C, °F, % or no specified unit
· Two modulating outputs with DC 0...10 V signal outputs, direct or reverse
action
· One digital input for day/ night changeover
· Entering or changing of all data via operating buttons on the controller, possi-
ble without additional tools
· PC connection for downloading canned applications via the software tool
The universal controllers are intended for Heating, Ventilating, Air-Conditioning and
Refrigeration in comfort control plants. It can be mounted in a control panel or in the
ARG62.21/ARG62.22 housing on ducts, walls and in plant rooms.
3
RWD62
Building Technologies
342

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RWD62

  • Page 1 RWD62 RWD62 Universal Controller For comfort control in HVAC&R-Systems · Standalone electronic universal controller with P or PI response · Operating voltage in accordance to type AC 24 V · Control application selectable via Application Number · Active input scale can be selectable ·...
  • Page 2: Functions Summary

    Protective big enclosure for wall mounting ARG62.22 Software Tool S3341A031EN0 Equipment combinations The following Siemens units can be connected to RWD62 universal controller. Units Data sheet no. Sensor with LG-Ni 1000 temperature sensing element 17… to 19… Sensor with Pt 1000 temperature sensing element 1846 Sensor with DC 0…10 V measuring signal...
  • Page 3: Main Functions

    Functions Controller type The RWD62 is a stand-alone universal controller, which performs both primary and auxiliary control functions. The respective mode is defined by entering the correspond- ing configuration and setting parameters via the push buttons on the controller or the software tool.
  • Page 4: Auxiliary Functions

    Active measurement from 0…10 V DC corresponding adjustable range from –100 to 8000 Passive measurement from 0…1000 W corresponding Temp. RWD62 adjustable range from –100 to 8000 Cascade control 4/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...
  • Page 5 Setpoint compensation The temperature setpoint X1 is shifted by the tem- perature as measured at sensor X2. Configuration of the RWD62 defines the influence on setpoint X1. The example shows the room air temperature setpoint as controlled by the outside temperature.
  • Page 6 Terminals Plug-in screw terminals Operating and display The RWD62 is operated by the buttons on the controller front. Additional tools are not elements necessary. A 9-pin port is provided for optional programming via the software tool. The LCD shows the following information for normal operation: ·...
  • Page 7: Installation Notes

    Standard cables can be used for the controller. However, when mounting in an envi- ronment greatly exposed to EMI, use only shielded cables. The RWD62 is designed for AC 24 V operating voltage. The low voltage must comply with the requirements for safety extra-low voltage (SELV) as per EN 60730.
  • Page 8 Screw terminals for cables with min. 0.5 mm dia. Terminals max. 2 x 1.5 mm or 2.5 mm Weight without packag- RWD62 0.277 kg The documents can be downloaded from http://siemens.com/bt/download. 8/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...
  • Page 9: Internal Diagram

    Signal input (aux. input: LS Ni 1000, Pt 1000, 0 …10 V DC and 0…1000 W or 0…10 V DC remote setpoint) Y1, Y2 Analog outputs Tool Communication port for PC (9-pin plug) Connection diagram 9/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...
  • Page 10 RWD62 ARG62.21 = 150 ARG62.21 / ARG62.22 ARG62.22 = 345 61.5 Published by: Siemens Switzerland Ltd. © Siemens Switzerland Ltd 2017 Building Technologies Division Delivery and technical specifications subject to change International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies...

Table of Contents