1-5-2. Rack Mounting Procedure

This section describes the rack mounting procedure using
the RMM-10 rack mount kit.
n
Tighten the screws to the following torque.
Tightening torque : 120 x 10
1. Attach the rack tool to the side of the equipment using
the specified six screws.
n
Use B4 x 6 screws.
Rack tool
B4 x 6
2. Loosen the screws on the rear of the right and left
adaptors and adjust the length of the adaptor according
to the depth of the rack.
(The illustration below shows the left adaptor.)
Adaptor
Portion of
the rail
n
Maximum depth of adaptor : 750 mm
Minimum depth of adaptor : 595 mm
1-6 (E)
_2
N.m {12.2 kgf.cm}
B4 x 6
Rack tool
B4 x 6
3. Attach the right and left adaptors to the rack complete-
ly using the specified six screws.
(The illustration below shows the left adaptor.)
B4 x 10
1U
31.75
4. Tighten the screws (B4 x 6 : two screws each on the
right and left) for adjusting the length of the adaptor
completely (the screws that were loosened in step 2).
5. Align the groove of the rack tool at the side of the
equipment with the rail, and slide the equipment to the
rear.
n
The rack tools are hooked on the rails as shown below.
Rack tool
Rail
6. Fix the rack angle in the rack using the specified screws.
Rack
Rack angle
B5 x 12
B5 x 12
31.75
B4 x 10
Unit : mm
Rack tool
Rail
Rack angle
BCU-100 IM