1.5
Technical Data
Digital inputs
Digital outputs
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
Type
Number
System
Limit frequency
Minimum pulse duration
(for high and low)
Signal level
Input current
Potential isolation
Maximum signal rise time
Permissible cable length (shielded)
Connection
Number
Signal level
Output current (short- -circuit proof)
Switching frequency
Cable length
Connection
Product Overview
Pulse counter
8
Incremental
Max. of 10 kHz
40 msec
24 Volt signals:
S
²
²
- -
Signal
H
: 15 to 30 Volt
²
²
- -
Signal
L
: -3 to +5 Volt
S
5 Volt signals:
²
²
- -
Signal
H
: 2.4 to 6 Volt
²
²
- -
Signal
L
: - -0.6 to 0.8 Volt
²
²
For 24 V and
H
signal
S
- -
Typical
4.7 mA
²
²
S
For 5 V and
H
signal
- -
Typical
10 mA
Yes
²
²
²
²
From
L
to
H
: typ. 10 msec
²
²
²
²
From
H
to
L
: typ. 15 msec
For 24 V
25 m
For 5 V
5 m
25- -pin sub D socket
8
24 Volt, P- -switching
Per DO:
Max. of 0.5 A
Total current:
Max. of 4 A
Max. of 10 Hz with ohmic load
8 Hz with lamp load
Max. of 0.5 Hz with inductive load
Max. of 100 m
15- -pin sub D socket
1-9