Siemens SITRANS LG260 Operating Instructions Manual page 87

Guided wave radar. four-wire modbus converter version in second chamber rod and cable probe
Hide thumbs Also See for SITRANS LG260:
Table of Contents

Advertisement

ScadaPack
Wiring plan
Fig. 49: Connection of SITRANS LG260 to RTU ScadaPack
1
SITRANS LG260
2
RTU ScadaPack
3
Voltage supply
Parameter
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The basic number of the input registers is always added to the input register address of SITRANS
LG260.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
PBD-51041059
1
+8
+30 Vdc
to
GND
2
SITRANS LG260 - Operating Instructions
COM Part 3 (C3)
RS485
1
2
TXD-
3
TXD+
4
GND
5
3
Value
9600
0
Floating Point
30001
6
7
8
9