ABB i-bus
EIB / KNX
4.4.4
Parameter window:
"Forced operation"
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
The function can be activated and deactivated via the object "Forced
operation". During a forced operation, the actuator triggers a freely
adjustable forced position which can no longer be changed. This has the
highest priority i.e. it is not modified by a valve purge or safety position.
Parameter: "Valve position during forced positioning"
The valve position triggered by the actuator during the forced operation is
defined in this parameter. The switch cycle time t
in the parameter "PWM cycle time for continuous control".
of the control is defined
CYC
47