Section 21
Basic IED functions
GPS+LON
•
GPS+BIN
•
SNTP
•
GPS+SNTP
•
IRIG-B
•
•
GPS+IRIG-B
PPS
•
CoarseSyncSrc which can have the following values:
Disabled
•
SPA
•
LON
•
DNP
•
IEC 60870-5-103
•
The function input to be used for minute-pulse synchronization is called BININPUT. For a
description of the BININPUT settings, see the
The system time can be set manually, either via the local HMI or via any of the communication
ports. The time synchronization fine tunes the clock (seconds and milliseconds).
The parameter
within a Substation Automation System, for IEDs connected in a communication network (IEC
61850-8-1). The
Disabled
•
•
SNTP -Server
21.13.2.3
Process bus IEC 61850-9-2LE synchronization
When process bus communication (IEC 61850-9-2LE protocol) is used, it is essential that the
merging units are using the same time source as the IED. To achieve this, a satellite-controlled
clock shall provide time synchronization to the IED (either internal GPS or via IRIG-B 00x with
IEEE1344 support) and to the merging units (via for instance PPS). For the time synchronization of
the process bus communication, GPS Time Module (GTM) and/or IRIG-B module can be used. If the
IED contains a GTM, the merging unit can be synchronized from the PPS output of the GTM.
502
SyncMaster defines if the IED is a master, or not a master for time synchronization
SyncMaster can have the following values:
Set the course time synchronizing source (
time synchronization of line differential function is used. Set the fine time
synchronization source (
complete time synchronization. GPS alone shall synchronize the analogue values in
such systems.
All protection functions will be blocked if the AppSynch parameter is set to Synch
while there is no 9-2 synchronization source. For more information please refer to
the "IEC/UCA 61850-9-2LE communication protocol" section.
Technical Manual .
CoarseSyncSrc ) to Disabled when GPS
FineSyncSource ) to GPS . The GPS will thus provide the
1MRK 511 358-UUS A
GUID-6E384BDB-5598-4108-99B4-0B4A4E1828B2 v3
Application manual