Bay Control (Qcbay) - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Control
5 = All
6 = Station
7 = Remote
PSTO = All, then it is no priority between operator places. All operator places are allowed to
operate.
According to IEC61850 standard the
Table 29: orCat attribute according to IEC61850
Value
0
1
2
3
4
5
6
7
8
13.3.1.1

Bay control (QCBAY)

The Bay control (QCBAY) is used to handle the selection of the operator place per bay. The
function gives permission to operate from two main types of locations either from Remote (for
example, control centre or station HMI) or from Local (local HMI on the IED) or from all (Local and
Remote). The Local/Remote switch position can also be set to Off, which means no operator place
selected that is, operation is not possible either from local or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set to discriminate between
commands with orCat station and remote (2 and 3). The selection is then done through the
IEC61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different apparatuses within
the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
292
1,2,3,4,5,6
2,4,5,6
3,4,5,6
Description
not-supported
bay-control
station-control
remote-control
automatic-bay
automatic-station
automatic-remote
maintenance
process
orCat attribute in originator category are defined in
1MRK 511 358-UUS A
Table 29
M16595-3 v7
Application manual