CTB1-27 through CTB1-28
CTB1-20 through CTB1-22
CTB1-31 through CTB1-32
CTB1-33 through CTB1-34
With Smoke purge option, After C20 Procedure follow below instruction
Smoke purge option is not available in Disconnect Drive Panels
Main menu
Parameter data set...with down arrow
Ok
E - ## Digital In/Out
Ok
E-0 # Digital Inputs
OK
Down arrow – 5 tines
Ok
SET TO [14] Jog
Ok
DEH40608 – Page 6
Analog Output 0/4-20 mA.
NOTE: 4-20 mA output signal will be available from the drive at terminal 39 and
42, which is wired for customer to terminal board CTB1-27 and CTB1-28.
Connect customer supplied 0-10 VDC or 4-20 mA "Auto" speed reference signal.
This signal functions as the drive's speed reference when the H-O-A switch is in
the "Auto" position. If utilizing a 0-10 VDC signal, CTB1-20 and CTB1-22 are to
be used. If utilizing a 4-20 mA signal, CTB1-20 and CTB1-21 are to be used.
CTB1-20 is the common terminal for either input signal. See the customer
interface diagram for details
These positions come with a jumper from the factory. Put normally open enable
contacts between CTB1-31 and CTB1-32. Closure between the contacts is
required for the motor to run in either drive or Bypass mode.
Smoke Purge circuit.
32
AN 11-2021 Rev 05, 12/15/2011