Troubleshooting - GE AF-600 FP User Manual

Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

6. Troubleshooting

If careful attention to phase rotation is not made during connection of the panel to the three-phase power
supply and motor, then there is only a one chance in four that the motor will rotate correctly in both drive and
bypass modes.
The other three possibilities and the corresponding corrective actions are as follows:
Problem: Motor turns correctly in Bypass mode and incorrectly in Drive mode
Solution: Swap two of three power supply leads AND two of three motor leads
Problem: Motor turns correctly in Drive mode and incorrectly in Bypass mode
Solution: Swap two of three power supply leads
Problem: Motor turns incorrectly in both modes
Solution: Swap two of three motor leads
Note that if the rotation in bypass mode is opposite to the rotation in drive mode, it is possible that the panel's
motor overload will trip if a full-speed transition between modes is attempted. This is due to the large amount
of current required to decelerate the motor to a stop prior to accelerating it in the correct direction.