Create Own Plant Web - Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

Prerequisites
Create plant web page
Note
Add data point element
Siemens
Building Technologies
5.6
Create own plant web pages
You can generate complete plant web pages yourself. As an option, you can
change and extend any imported plant diagrams (see Section 5.5) as needed.
This section presents the steps required to generate and design a customized
plant web page.
· The drafter is logged on to the Web Server as an administrator.
· The Web Server is connected via KNX with one or more devices.
· The device web pages for the Web Server and devices are generated, see
Section 2.4. The Web Server menu tree and data point information is now
available.
The following describes how to create a plant web page and add a background
image.
1.
Go to home nodes or to a device node.
2.
Click New.
The properties dialog box is displayed.
3.
In the Displayed name field, enter the name for the plant web page
(is displayed later in the navigation area for the Web Server).
4.
Click the red pencil in the Background picture field.
The add dialog box is displayed.
5.
Search to go to the desired background picture.
6.
Click Open.
7.
Click Upload.
The file name for the selected picture is displayed in the background
picture field.
8.
Click OK.
The plant web page is now saved with the background picture.
The anchor for the X/Y position of the background image is fixed on the plant web
site in the full image at180/194 pixels (left top corner of the image). This
corresponds to 10/86 pixels in the partial view.
The following describes how to add a data point element to a newly created
plant web page.
1.
Click Edit.
The plant web page switches to edit.
2.
Click Data point.
The data point dialog box is displayed.
3.
Click the red pencil in the Data point address field.
The data point address dialog box is displayed.
4.
Go to the data point via device, menu text(s).
5.
Select Data point.
The entire data point path is entered in the data point address field.
6.
Set the X/Y position for the data point field in the display area.
7.
Modify formats such as text field size for "Data point" and "Data point" as
needed.
8.
Click Apply to check the results of the change in formatting as a preview to
the plant web page.
9.
If satisfied, click OK to finish.
10. Click OK to change to view.
The data point value was read and is displayed.
Web server OZW772... V6.0
Visualize plants
69 / 176
CE1C5701en
2015-10-12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents