Diagnostics
Device information
Notes
Web Server
KNX
Ethernet
Siemens
Building Technologies
4.2.3

Web Server diagnostics

The following information is required to identify product version and settings.
Information on faults is available in Section 4.3.2.
The device information identified the Web Server.
Entries on the operating page "Device information" our for information purposes
only and cannot be edited here.
Path: Home > 0.2.150 OZW772.xx > Device information > Web Server.
Data point
Plant name
Web Server type
Fabrication number
System definitions
Software version
Build
Hardware version
Message inhibition
Activation key
The following information displays the current settings and states on the KNX bus.
The KNX settings are in Section 2.5.3, Operating page "Settings".
Path: Home > 0.2.150 OZW772.xx > Device information > KNX.
Data point
Area
Line
Device address
Clock time mode KNX
Clock slave remote adj
KNX
Number of devices max Maximum possible number of devices monitored
Number of devices
current
Last change
Web server OZW772... V6.0
Operate using a web browser
Explanation, example
Web Server or plant name.
Web Server product number (ASN).
Device number from production
Version of the loaded system definitions
Web Server software version.
Revision status for the software.
Web Server hardware version.
Displays position of switch 8 "Message inhibition"
Activation key for registering on the Synco IC
portal
Explanation, example
First KNX network level.
The line coupler assigns the area. The factory
setting for the Web Server is set to area 0.
Second KNX network level.
The line coupler assigns the line. The factory
setting for the Web Server is set to line 2.
The factory setting for the Web Server is set to
device address 150.
"Master" or "Autonomous": Time is mapped from
Web Server quartz.
"Slave": the Web Server gets the time from the
master clock.
"Clock slave remote adj KNX" = "Yes" allows the
Web Server to change the clock master time on
the KNX network.
"Yes" makes sense for "Time synchronization" =
"Slave on bus".
by Web Server on the Synco bus.
Actual number of devices monitored by Web
Server on the Synco bus.
Time of last change to device list.