Commissioning
9
Set Windows firewall
102 | 124
Building Technologies
Fire safety
6. Click 'Next >' to confirm and enter the program path to
'WebEngineeringServer.exe'.
Example: D:\Program Files\Siemens\Offline Web
Tool\offline_server\api\thrift\WebEngineeringServer.exe
7. Click 'Next >' to confirm and then confirm the default setting 'Allow the
connection' in the next step ('Action').
8. In the next step 'Profile', remove the check mark from the 'Domain' checkbox.
a The 'Private' and 'Public' checkboxes are checked.
9. Click 'Next >' to confirm and enter an appropriate name in the next step
('Name'), such as 'FC360 Desktop Editor‑application'.
10. Click 'Finish' to complete the process.
a A 'New Rule' has now been set and appears in the 'Inbound Rules' list.
Additional settings are required for the new rule:
1. Right-click the new rule and select 'Properties'.
2. Select the 'General' tab in the 'Rule Name Properties' window.
3. Set the following values:
'General': 'Activated'
'Action': 'Allow connection'
4. Select the 'Protocol and Ports' tab.
5. Set the following values:
'Protocol type': 'UDP'
'Local port': 'Specific Ports', and enter the value range '69' in the box.
'Remote port': 'All Ports'
6. Confirm with 'OK'.
a The new firewall rule is now configured.
NOTICE
Unauthorized access to your PC
Deactivate the firewall rule configured above after the firmware update.
A6V10421795_en--_g
2016-11-18