75
Grid supply connection
• Remove the protective cover. Connect the grid cables to grid terminals L1, L2 and
L3. See the chapter
Technical
data.
• Tighten the cable lead-through grommets and seal them properly.
• Assemble the cooling fan and protective covers. Close the door.
The recommended cable types are given in the chapter
Planning the electrical
installation.
The rotor connections are located behind the power modules. The following figure
shows the connectors inside the cabinet.
Protective earth cable may be connected to PE busbar under any free bolt. Note that
marked bolts are mounting bolts of the PE busbar and are not for connecting the PE
cables.
Electrical installation