ABB PSTX Series Installation And Commissioning Manual page 107

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

7.17.10 Phase reversal protection
This protection senses if the phases are connected
incorrectly.
The order in which the phases are connected to the
in-stream power has no effect on the Softstarter, but it
may be relevant to the motor, which is connected to the
Softstarter. The motor can for example run in the wrong
direction if the phases are connected incorrectly. This
protection senses if the phases are connected in the
wrong order and then prevents the engine from starting.
Phase reversal protection has these parameters
Parameter
16.01 Phase rev out
16.02 Phase rev operation
16.12 Phase rev expected sequence
7.17.11 Frequence range protection
Sets the trip level for the frequency.
Frequency range protection has these parameters:
Parameter
16.03 Freq range lower trip lvl
16.04 Freq range upper trip lvl
16.05 Freq range trip time
16.06 Freq range out
16.07 Freq range operation
7.17.12 Bypass open protection
This protection senses if the Bypass contactor or relay
did not close when Top of ramp is reached.
Speak to ABB Sales Offices for service.
Bypass open protection has these parameters:
Parameter
16.08 Bypass open out
16.09 Bypass open operation
Description
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Expected phase sequence
Description
Sets the lower trip level for the
frequency.
Sets the upper trip level for the
frequency.
Sets the time that the frequency is
outside the trip range to trip.
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Description
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
1SFC132081M0201
| Installation and commissioning manual | Functions
Setting range
Default value
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto, Indication.
L1_L2_L3, L1_L3_L2,
L1_L2_L3
Unknown
Setting range
Default value
40 ...72 Hz
45 Hz
40 ...72 Hz
66 Hz
0 ... 60 s
5 s
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto, Indication.
Setting range
Default value
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Indication
Stop auto, Indication.
7
107