7.17.7
Overvoltage protection
This protection senses if the main voltage is too high.
This protection does not operate in the Standby state.
Overvoltage protection has these parameters:
Parameter
15.01 Overvoltage level
15.02 Overvoltage trip time
15.03 Overvoltage out
15.04 Overvoltage op
7.17.8
Under voltage protection
This protection only operates in the Top of ramp state.
Under voltage protection has these parameters:
Parameter
7
15.05 Under voltage level
15.06 Under voltage trip time
15.07 Under voltage op
15.08 Under voltage out
7.17.9
Voltage imbalance protection
This protection senses voltage imbalance. Normally
there is the same voltage in all 3 phases. If the voltage is
different in the phases, the engine can run bumpy.
Voltage imbalance protection has these parameters:
Parameter
15.09 Voltage imb level
15.10 Voltage imb out
15.11 Voltage imb op
15.11 Voltage imb trip time
106
Functions | Installation and commissioning manual |
Description
Sets the Overvoltage trip level.
Sets the time that the voltage is
above the trip level to trip.
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Description
Sets the Under voltage trip level.
Sets the time that the voltage is
below the trip level to trip.
Sets the operation of this
protection.
Identifies the Event groups this
protection is part of.
Description
Sets the permitted voltage
imbalance level between the
phase with the highest voltage
and the phase with the lowest
voltage.
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Sets the time of voltage
imbalance in order to trip.
1SFC132081M0201
Setting range
Default value
165 ... 850 V
850 V
0.1 ... 100.0 s
1.0 s
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto, Indication.
Setting range
Default value
165 ... 760 V
165 V
0.1 ... 100.0 s
1.0 s
Off, Stop manual,
Off
Stop auto, Indication.
Eventgroup 0 ... 6
0000010
Setting range
Default value
1 ... 100%
10%
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto,
Indication.
1...100 s
10 s