R 02/92
This special function allows you to use software to inhibit all interrupts of the module.
The function is selected by transfer of E3, and deselected with another transfer of E3.
The status of bits 5 and 6 in response message byte 7 (module address +7) indicates whether this
function is active.
Function active: bit 5 = 1
bit 6 = 1
The module does not trigger illegal interrupts during reparameterization and during changing cam
setpoints.
n = O
The function is selected by transfer of E4, and deselected by another transfer of E4.
The status of bit 6 in response message byte 7 (module address +7) indicates whether this special
function is active.
Function active: bit 6 = 1
1) This function is implemented as of firmware release R09. The standard function blocks sup-
port the special function starting with the release states given in the technical specifications
AG 1969, Order No:'6ES5 998-0KD21