Information on control cabinet cooling

10.8.1

General

Electrical cabinets can be cooled, using among other things with the following:
● filtered fans
● heat exchangers or
● cooling units.
The decision in favor of one of these methods depends on the prevailing ambient conditions
and the cooling power required.
The air routing inside the control cabinet and the ventilation clearances specified here, must
be carefully observed. Other components or cables must not be installed/routed in these
areas.
You must comply with the following specifications when installing SINAMICS components:
● Cooling clearance
● Cable routing
● Air guidance, air-conditioner
Table 10- 19 Ventilation clearances around the components
Component
CU310-2 DP
CU310-2 PN
CUA31
SMCxx
Line filter
Line reactor
PM240-2 Blocksize, frame size FSA ... FSC
PM240-2 blocksize, frame size FSD ... FSF
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Cabinet design and EMC for components, Blocksize format
10.8 Information on control cabinet cooling
Clearance above and below
in mm and (inches)
50 (1.97)
50 (1.97)
50 (1.97)
50 (1.97)
100 (3.93)
100 (3.93)
Above: 80 (3.15)
Below: 100 (3.93)
Above: 300 (11.81)
Below: 350 (13.78)
Clearance in front of the
component
in mm and (inches)
100 (3.94)