Parameter Descriptions
Digital input function
Counter B (up)
Counter B (down)
Reset Counter B
Mech. Brake Feedb.
Mech. Brake Feedb. Inv.
PTC Card 1
Table 3.6
AF-650 GP standard terminals are 18, 19, 27, 29, 32 and 33. OPCGPIO General Purpose I/O Option Module terminals are
X30/2, X30/3 and X30/4.
Functions dedicated to only one digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
No reaction to signals transmitted to the
operation
terminal.
[1]
Reset
Resets frequency converter after a TRIP/
ALARM. Not all alarms can be reset.
[2]
Coast
Coasting stop, inverted input (NC). The
inverse
frequency converter leaves the motor in free
mode. Logic '0' => coasting stop.
[3]
Coast and
Reset and coasting stop Inverted input (NC).
reset inverse
Leaves motor in free mode and resets
frequency converter. Logic '0' => coasting
stop and reset.
[4]
Quick stop
Inverted input (NC). Generates a stop in
inverse
accordance with quick-stop ramp time set in
C-23 Quick Stop Decel Time. When motor
stops, the shaft is in free mode. Logic '0' =>
Quick-stop.
[5]
DC-brake
Inverted input for DC braking (NC). Stops
inverse
motor by energizing it with a DC current for
a certain time period. See B-01 DC Brake
Current to B-03 DC Brake Cut In Speed [RPM].
The function is only active when the value in
B-02 DC Braking Time is different from 0.
Logic '0' => DC braking.
[6]
Stop inverse
Stop Inverted function. Generates a stop
function when the selected terminal goes
from logical level '1' to '0'. The stop is
performed according to the selected ramp
time (F-08 Decel Time 1, E-11 Decel Time 2,
E-13 Decel Time 3, E-15 Decel Time 4).
NOTE
When the frequency converter is at the
torque limit and has received a stop
command, it may not stop by itself. To
ensure that the frequency converter
stops, configure a digital output to [27]
Torque limit & stopand connect this
digital output to a digital input that is
configured as coast.
AF-650 GP Programming Guide
Select
[63]
[64]
[65]
[70]
[71]
[80]
[8]
Start
[9]
Latched
start
[10] Reversing
[11] Start
reversing
[12] Enable start
forward
[13] Enable start
reverse
[14] Jog
[15] Preset
reference on
[16] Preset ref bit
0
[17] Preset ref bit
1
[18] Preset ref bit
2
DET-618C
Terminal
29, 33
29, 33
All
All
All
All
(Default Digital input 18): Select start for a
start/stop command. Logic '1' = start, logic '0'
= stop.
The motor starts, if a pulse is applied for min.
2 ms. The motor stops when Stop inverse is
activated.
(Default Digital input 19). Change the
direction of motor shaft rotation. Select Logic
'1' to reverse. The reversing signal only
changes the direction of rotation. It does not
activate the start function. Select both
directions in H-08 Reverse Lock. The function
is not active in process closed loop.
Used for start/stop and for reversing on the
same wire. Signals on start are not allowed at
the same time.
Disengages the counterclockwise movement
and allows for the clockwise direction.
Disengages the clockwise movement and
allows for the counterclockwise direction.
(Default Digital input 29): Use to activate jog
speed. See C-20 Jog Speed [Hz].
Shifts between external reference and preset
reference. It is assumed that [1] External/preset
has been selected in F-54 Reference Function.
Logic '0' = external reference active; logic '1'
= one of the eight preset references is active.
Preset ref. bit 0,1, and 2 enables a choice
between one of the eight preset references
according to the table below.
Same as Preset ref bit 0 [16].
Same as Preset ref bit 0 [16].
3
3
43