Installing The Wiring - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Ratings and frame size
The charts in the Ratings section of the ACH580-01 Hardware Manual
(3AXD50000044839) list technical specifications, and identify the drive's frame size.
Note: Some instructions in this document vary, depending on the drive's frame size.
To read the Ratings table, you need the "Output current rating" entry from the
code
Suitable mounting location
For selecting a suitable mounting location for PCR/PDR configurations, refer to:
• The ACH580-01 Hardware Manual (3AXD50000044839), and
• The
information on dimensions and weights
• UL (NEMA) Type 3R, Px3R-1...Px3R-4 enclosures are designed to be mounted
on a wall. Mounting these 3R enclosures on an open rack system requires the
use of the supplied 3R enclosure back plates to maintain 3R integrity.

Installing the wiring

Wiring requirements
The wiring requirements apply to all ACH580 drives. In particular:
• Use separate, metal conduit runs for the following different classes of wiring:
– Input power wiring.
– Motor wiring.
– Control/communications wiring.
• Properly and individually ground the drive, the motor and cable shields.
(see page 226).
Technical data
section on page
237
in this manual for the appropriate
227